Features
- Presence detector (PIR)
- Square detection area
- Genuine daylight measurement
- Light switch output (relay, 230 V)
- Presence switch output (relay, potential-free)
- Automatic control of lighting and HVAC as well as room monitoring function
- Lighting control with light threshold value and self-learning swich-off delay
- Choice of fully or semi automatic operation
- Sensor or switch options for manual switching
- Pulse function for staircase time switch
- Inrush current limitation for EB
- HVAC control with switch-on and swich-off delay
- Room monitoring with selective movement detection
- Fully or semi-automatic: In 'Fully automatic' mode, the lighting switches on and off automatically according to presence and light. In 'Semi-automatic' mode, it must be switched on manually and it switches off automatically
- Manual override: The lighting can be manually switched on or off at any time via sensors or switches
- Room/corridor sensor function: In the 'corridor' setting, the detector functions as a staircase time switch and it cannot be switched off manually
- The pulse function is for controlling a staircase time switch
- The inrush current limitation makes the presence detector particularly suitable for switching electronic ballasts (EBs)
- The presence detector has 'Genuine daylight measurement' and is only suitable for switching fluorescent lamps (FL/PL)
- Presence switch contact for HVAC control: The switching behaviour of the potential-free contact is only controlled by presence
- The switch-on delay prevents instantaneous switch on. The contact only closes on completion of the switch-on delay
- The sensitivity of the presence switch output is reduced in the 'monitoring' position. The contact indicates the presence of people with a high degree of certainty
- Master/slave parallel switching: Up to ten detectors can be connected with each other to extend the detection area. The master switches the load. All other detectors merely provide presence information as slaves
- Device can be connected as master or slave
- Test operation mode checks the detection area and installation
- A maximum of 10 detectors can be switched at the same time
- The switching behaviour of the presence detector is controlled by presence and light
- The self-learning switch-off delay adjusts to occupants' behaviour
- The square detection area allows accurate and simple planning
Specifications
Operating voltage |
230 V AC |
Frequency |
50 Hz |
Recommended installation height |
2 – 3,5 m |
Installation type |
Ceiling installation |
Power consumption |
0,9 W |
Light measurement |
Genuine daylight measurement |
Setting range brightness |
10 – 1500 lx |
Light switch-off delay |
10 s-20 min |
Type of contact light |
Relay 230 V, switch-on current limit |
Lamps |
Fluorescent lamps |
Compact and flourescent lamps |
max. 1400 VA |
Compact and flourescent lamps (Number of electronic ballasts) |
16 x (1 x 58 W), 8 x ( 2 x 58 W), 24 x (1 x 36 W), 12 x (2 x 36 W), 24 x (smaller than 36 W) |
Switch-on delay presence |
0 s – 10 min |
Presence switch-off delay |
10 s-120 min |
Type of contact presence |
Relay potential-free |
Switching capacity presence |
100 W (50 V DC), 460 VA (230 V AC), minimal 10 V/100 mA |
Switching output |
Potential-free |
Type of connection |
Spring terminals |
Max. cable cross section |
1,5 mm² |
Mounting plate |
70 x 70 mm |
Size of concealed housing |
55 mm (NIS, PMI) |
Ambient temperature |
+0 °C … +50 °C |
Protection class |
II as per EN 60 730-1 |
Type of protection |
IP 40 |
- Hãng sản xuất THEBEN của Đức.
Mời bạn đánh giá hoặc đặt câu hỏi về THEBEN ECO-IR 360C NT