SB3
Bộ cách ly an toànBộ cách ly an toàn BOSCH SB3
- Bộ cách ly an toàn cho đầu dò và công tắc khẩn chống cháy nổ (bao gồm Module input/output DCA1192).
Bộ cách ly an toàn BOSCH SB3
- Bộ cách ly an toàn cho đầu dò và công tắc khẩn chống cháy nổ (bao gồm Module input/output DCA1192).
SB3 Safety Barrier incl. DCA1192 Input/Output Module
Functions
The SB3 Safety Barrier limits the electrical energy between non-inherently safe and inherently safe circuits and thus prevents the ignition of gas mixtures by electrical sparks. The Safety Barrier must always be installed outside the explosive area. The DCA1192 Input/Output Module is the galvanical isolation between the fire panel and SB3 Safety Barrier.
Technical Specifications
SB3 Safety Barrier, with Housing
- Max. voltage 28 V DC
- Max. permissible current 100 mA
- Max. output 0.7 W
- Wire gauge 0.2 mm2. . . 2.5 mm2
- Cable bushings PG16 (6x)
- Dimensions (W x H x D) 135 x 135 x 65 mm
- Housing material Plastic, PC
- Housing color White, RAL 9010
- Weight Approx. 450 g
- Protection class as per EN 60529 IP 56
- Permissible operating temperature -25 °C . . . +70 °C
- Permissible storage temperature -30 °C . . . +75 °C
- Ignition protection according to
- EN 50014/20
- Inherent safety EEx ia IIC / IIB
DCA1192 Input/Output Module, with Housing
- External supply
o Operating voltage 18 V DC . . . 32 V DC
o Current consumption Max. 5 mA
o Line resistance 50 Ω . . . 250 Ω
o Line termination EOL22(Ex)
- Line termination
o Operating voltage 18 V DC . . . 22 V DC
o Standby current ≤45 mA
o Operating current ≤150 mA
o Line resistance 50 Ω . . . 250 Ω
o Line termination EOL22(Ex)
- Wire gauge 0.2 mm2. . . 2.5 mm2
- Cable bushings PG16 (6x)
- Housing material Plastic, PC
- Housing color White, RAL 9010
- Dimensions (W x H x D) 135 x 135 x 65 mm
- Weight Approx. 425 g
- Protection class as per EN 60529 IP 56
- Permissible operating temperature -25 °C . . . +70 °C
- Permissible storage temperature -30 °C . . . +75 °C
- Permissible relative humidity ≤100% at T≤34 °C
Parts Included
- 1 SB3 Safety Barrier
- 1 Installation set for SB3
- 1 DCA1192 Input/Output Module
- 1 Terminal carrier for DCA1192
- 1 EOL22(Ex) line termination, included with the DCA1192
- 2 Housing with cover
Mời bạn đánh giá hoặc đặt câu hỏi về SB3